Feedback input terminal has disconnection detection function,add a 10K terminal resistance at one end,otherwise it will report as product feedback terminal
fault.Output line has disconnection and short line detection function,when module does no action,voltage between DC13V to 48V is required at normal open output terminal otherwise it will report asmodule output line fault.
Open installation applied for the module.Insert mode for installation between base and module.When
·Line detection function for input and output
·Input terminal is ste as normal open detecting function connected with passive contalt
·Non-polarized two-wire
·Active and passive output
Operating voltage | Loop:24V(18.5V~26V); Power:DC24V(DC19V~DC28V) |
Standby current | Loop:≤0.2mA; Power: ≤2mA |
Starting current | Loop:≤2mA;Power:≤22mA |
Operaing Environment | Temperature:-10℃~+55℃; Relative Humidity:≤95% non-condensing |
Output capacity | Passive:Capacity:DC30V/3A; Contact resistance in normal condition:100kΩ; Closed when activated;Suitable for DC or AC12V~48V; Active output:DC24V/1.5A |
Coding method | Electronically coding |
Code range | 1~255 |
Weight | About 147g(with base) |
Material and color of enclosure | ABS; Porcelain white |
Mounting hole distance | 60mm |
Dimension(L×W×H) | 86mm×38mm×86mm(with base) |