The FW811 input module monitors a single contact.The input line is monitored for open line faults and ground faults,and the contact must thus be wired with an end-of-line resistor.It is an intelligent addressable module and takes one address on the Signaling Line Circuit(SLC)or Data Communication Link(DCL)of the fire alarm control panel.The FW811 is a UL listed device according to UL864 and ULC-S527 for Fire Protective Signaling Systems for indoor use.The type of the input contact is configurable.
Alarm Causing:An alarm causing input will produce an ALARM event.The device LED will indicate the alarm condition by red steady on.A return to normal condition will be ignored and the device LED indicator will remain latched in the red alarm condition until a reset command has been received.
Supervisory/Trouble/Monitor Causing:By changing the FW811 input module functions from its attribute interface on FACP,it can be configured to be a supervisory,trouble,or monitor signal,which will produce a SUPERVISORY,TROUBLE,or MONITOR event.The device LED will indicate the event condition by red steady on.The supervisory and monitor are latched/non-latched selectable.A return to normal condition will cause the event to disappear and the device LED indicator will return to the normal condition if the supervisory/monitor is non-latched.A return to normal condition will not cause the event to disappear and the device LED indicator will remain in event condition if the supervisory/monitor is latched.The trouble is non-latched.
Nominal Voltage | 24VDC |
Voltage Range | 15 to 28VDC |
Standby Current | 0.17mA |
Alarm Current | 0.79mA |
Max.Line Impedance | 25Ω |
Max.Impedance for Grounding | 6.6 KΩ |
Compatible EOLR | FW421(10KΩ) |
Operating Temperature | 32°F to 120°F(0°C to 49°C) |
Operating Humidity | 0%to 93%RH |
Mounting | FW800 base |
Dimension | 120 mm(L)x 120 mm(W)x 45 mm(H) |
Weight(with backbox) | 8.7 oz(247 g) |
Wiring Gauge | 12 to 18 AWG |