Take surface installation for the isolator,install the base upward of the arrow direction,plug-in for theisolator to the base.Pull off the isolator,wear the cable through wiring hole on the base and connectcorrespondent terminal and plug in the isolator.Mounting hole distance is 60mm.
Wiring instruction:BS(pin 5),AS(pin 8):loop negative:BP(pin 6),AP(pin 7):loop positive
The positive cable inserts from pin 7 and out from pin 6.The cable negative inserts from pin 8 and out frompin 5.Please refer to control panel TC5109 terminal mark wiring.5.6 Recommended Cabling:1.0mm2 orabove fire cable,subject to local codes.
•Polarized connection with peripheral devices and no need to transfer connection of input and output.
•Delayed power supply to output terminal devices will avoid over load or strong transient current
•Plug-in structure
•Non-polarized two-wire
Operating voltage | Loop 24V(18.5V~26V) |
Operating current | Loop polling current≤5.5mA, loop activate current≤25mA |
Coding method | Electronically coding |
Indicator | Yellow,light out in normal condition,Illuminates in action |
Material and color of enclosure | ABS;Porcelain white |
Weight | 147g(with base) |
Mounting hole distance | 60mm |
Operating Environment | Temperature:-10℃~+50°℃; Relative Humidity:≤95%non-condensing |
Ingress protection rating | IP30 |
Dimension(L×W×H) | 86mm×41mm×86mm(with base) |