当宁消防网
天成消防 TCMK 5271 Zone Monitoring Interface
¥0.0媒体价 登陆后可见 市场价 询底价
天成消防 产品239件 进入品牌专区 33人 关注
证书
检验报告 英国LPCB认证
热度
图文详情 产品参数 评论 文章

年中大促

天成外贸产品

系统接线图

一、TCMK 5271 Zone Monitoring Interface的概述

TCMK5271 area monitoring interface (hereinafter referred to as interface) is mainly used to connect externalmulti-wire conventional detectors to the loop signal bus. It is used to monitor the status of external multi-lineequipment and transmit its status to the control panel through the bus. When any detector in the loop sendsan alarm signal, the area monitoring interface receives the information and uploads it to the control panel.

二、TCMK 5271 Zone Monitoring Interface的特点

▪It has the function of detecting the wiring fault of external multi-line equipment; 

▪The address code is electronically coded,which can be written in advance by the electronic encoder,and the engineering debugging is simple and reliable.

▪Wall-mounted,small size.

三、TCMK 5271 Zone Monitoring Interface的技术参数

Operating voltage Rated working voltage of signal bus: bus 24V range: DC16V~DC28V
Power supply rated working voltage: DC24V range: DC20V~DC28V
Operating current Bus monitoring current ≤0.25mA
Bus starting current ≤ 0.8ma.
Monitoring current of power supply ≤10mA
and starting current of power supply ≤25mA
Output capacity each interface can have up to 30 detectors.
Indicator light red, fire alarm light, shining during patrol inspection,
and always on. Yellow, fault light, always on.
Coding mode electronic coding mode, occupying one bus coding point,
and the coding range can bearbitrarily set between 1 and 255.
Wire Connect with the signal bus 2 of the control
panel and the power line
Environment Temperature:-10℃ ~+55℃
Relative humidity ≤95%, non-condensing.
Overall dimensions 86mm×86mm×40mm (with bottom shell)
Material and color ABS, porcelain white
Weight about 300g
Installation hole distance 60mm