The FireWatcherFW106S/FW106SC is an intelligent Fire Alarm Control Panel designed for small to medium-scale facilities.The FireWatcherFW106S/FW106SC is ideally suited for both new and retrofit commercial,institutional,and industrial fire detection and notification applications.The only difference between FW106S and FW106SC is the language.FW106S is in English and FW106SC is in French.
Specifications and Features
General
Digital signal processor based design,fully configurable from front panel with password protection
Environmental
Operating temperature:32-120°F(0-49℃)
Relative humidity:Up to 93% 90°F(32℃)
To be installed in normal dry indoorenvironment only
Primary Supply
110-120 VAC 60Hz(3.86A),or
220-240 VAC 50Hz(1.96A)
SecondaryPower Supply
Two 12V in series lead-acid batteries set
Charging capacity:40AH
Power Outputs
Internal power supply for:
AMI
ALUs and Addressable Loop Circuits
NOUs and Notification Appliance Circuits
XNUs,External Network Circuits
ROUs
One auxiliary power supply:
Non-Resettable/Resettable Power Output(configurable)
Power limited
24VDC
Output current:500mA in normal standby,1200mA in alarm
Power Factor Rating:0.35
Special application:Compatible devices are the Annunciator Model FW121/FW121C/FW122W/FW122R/FW122CW/FW122CR and IO Module Model FW821.
CLASS B when powering annunciator models FW121/FW121C/FW122W/FW122R/FW122CW/FW122CR
Relays Output
One programmable relay
4 non-programmable status relays
Status:Alarm,Supervisory,Trouble,Monitor
Form C Contact
Contact Rating:2A 30VDC
Power Factor Ration:0.35
Notification Appliance Circuits
Total of 4 circuits supported,total power available 8A
2 Class A or 2 Class B circuits on each NOU
Maximum Current:2A per NAC circuit
Alarm Voltage:24V nominal
Bell code:Temporal 3
Panel supports one regulated 24 VDC NAC,or four specialapplication24VDC NAC.Refer to Table 20 for specific appliances/devices.
Max line loss:1.8 V.
Network Circuit
Class B circuit
For up to 110 panels and/orremote annunciators connection